I have been designing fire suppression systems for 30 years. NFPA 13 does not require systems to battle multiple fires. There can be project specific requirements that mandate this but code minimum NFPA 13 does not. More than likely this warehouse was protected by ESFR sprinklers, which when flowing all 12 sprinklers that are required to be calculated, would put out a flow more than most public water systems can handle.
NFPA 25 has nothing to do with design criteria and is focused on inspections.
They just finished building what was supposed to be a battery manufacturing facility in Kernersville but is sitting empty. My assumption is they are repurposing that facility for this new excavator plant.
Being an illegal immigrant and committing murder or rape should come with a death sentence. No deportations. Just a speedy trial and if convicted then you get the bullet within the week.
I have been designing fire suppression systems for 30 years. NFPA 13 does not require systems to battle multiple fires. There can be project specific requirements that mandate this but code minimum NFPA 13 does not. More than likely this warehouse was protected by ESFR sprinklers, which when flowing all 12 sprinklers that are required to be calculated, would put out a flow more than most public water systems can handle.